Notification 635 -– Harmonic Limit Exceeded |
||
CATEGORY |
ISSUE / RESULT |
FIX / REFERENCE(S) |
Information |
The limits for one or more harmonics have been exceeded. |
|
For Power Supplies above 25W the standard IEC61000-3-2 defines the maximum allowed individual current harmonics allowed on the AC input.
By lowering the KP of a design you are guaranteeing lower harmonic distortion.
Harmonic order (n) |
Maximum permissible harmonic current expressed as a percentage of the input current at the fundamental frequency (%) |
2 |
2 |
3 |
30•λ * |
5 |
10 |
7 |
7 |
9 |
5 |
11≤n≤39 (odd harmonics only) |
3 |
* λ is the circuit power factor